VFD Fault — Overcurrent

50001

Variable frequency drive tripped on overcurrent protection. Motor stopped immediately.

high conveyor piler packaging palletizer
vfd drive overcurrent motor overload

Probable Causes (ranked)

Fix Steps

  1. 1 Check motor and driven equipment for mechanical binding — try to rotate by hand
  2. 2 Megger motor windings — insulation resistance should be greater than 1 Megohm to ground
  3. 3 Inspect motor cable connections at VFD output terminals and motor terminal box — tighten all
  4. 4 Review VFD fault log for pattern — single event vs recurring at same point in cycle
  5. 5 Increase acceleration ramp time if fault occurs during motor start
  6. 6 If motor and wiring test good, VFD output section may need factory service

Suggested Replacement Parts

Parts matched to fault category: Vfd Drive

Allen-Bradley PowerFlex 525 AC Drive 1HP P/N: 25B-D2P3N114 1HP, 480V, 3-phase, built-in EtherNet/IP, EMC filter
ABB ACS580 General Purpose Drive 2HP P/N: ACS580-01-05A7-4 2HP, 480V, built-in safe torque off, adaptive programming
GS20 AC Drive 1HP (Budget Option) P/N: GS20-20P5 1HP, 230V, sensorless vector, compact size — good replacement for testing