VFD Fault — Ground Fault

50003

VFD detected current leakage to ground on motor output circuit. Drive tripped to protect equipment.

high conveyor piler packaging palletizer
vfd drive ground fault insulation motor

Probable Causes (ranked)

Fix Steps

  1. 1 Disconnect motor leads at VFD — megger each phase to ground, all should read over 1 Megohm
  2. 2 Inspect motor cable entire run for physical damage — pay attention to conduit entry points
  3. 3 Open motor terminal box — check for moisture, corrosion, or water pooling
  4. 4 If cable and motor test good, adjust VFD ground fault sensitivity threshold per manual
  5. 5 Seal all cable glands and conduit entry points with appropriate sealant