RepairXpert Industrial Automation

Communication Timeout — DeviceNet

60005

DeviceNet node has stopped communicating. Scanner reports node offline and associated I/O data is invalid.

high general conveyor packaging palletizer
communication devicenet network timeout scanner node

Probable Causes (ranked)

Fix Steps

  1. 1 Check DeviceNet cable connections at the faulted node — push connectors fully in
  2. 2 Measure 24VDC at the faulted node DeviceNet port — should be between 11V and 25V
  3. 3 Verify 121 ohm termination resistors are installed at both physical ends of the trunk
  4. 4 Check node MAC address DIP switches — compare to scanner configuration
  5. 5 Power cycle the faulted node and watch for it to come back online in scanner diagnostics
  6. 6 If node does not return, try replacing with spare and setting same MAC address

Suggested Replacement Parts

Parts matched to fault category: Network Module

Allen-Bradley 1756-EN2T EtherNet/IP Module P/N: 1756-EN2T ControlLogix EtherNet/IP module, dual port, DLR capable
Siemens CM 1542-1 PROFINET Module P/N: 6GK7542-1AX00-0XE0 S7-1500 PROFINET IO controller, 2-port switch
Managed Industrial Ethernet Switch 8-Port P/N: SE2-SW5U 8-port managed switch, DIN rail, 10/100 Mbps, IGMP snooping

Prices are estimates. Verify part numbers match your equipment before ordering.