A periodic or event task in the ControlLogix controller exceeded its configured watchdog time. The task was aborted. If this is the safety task, safety outputs go to their configured fault state.
Go to Controller Properties > Tasks and look at the 'Max Scan Time' column. If max scan time is within 80% of the task period, you're one load spike away from a watchdog trip. Best practice is max scan should be below 50% of the period to leave headroom.