AB-F007

ControlLogix redundancy pair performed a switchover. Secondary processor took over from primary.

critical allen-bradley
allen-bradley redundancy switchover controllogix

Probable Causes (ranked)

Fix Steps

  1. 1 Check which processor is now primary in Controller Properties
  2. 2 Inspect original primary for fault codes — resolve root cause
  3. 3 Verify redundancy link cable is secure between chassis
  4. 4 Check power supply status on both chassis
  5. 5 If switchover was unexpected, investigate and fix before clearing alarm

Field Trick

The blue LINK LED on both 1756-RM2 modules should be solid. If one is off, the redundancy link is broken.