RepairXpert Industrial Automation

Point I/O Adapter Communication Loss

AB-F010

1734 Point I/O adapter lost communication with the ControlLogix/CompactLogix processor over EtherNet/IP.

high allen-bradley
allen-bradley point io 1734 ethernet adapter

Probable Causes (ranked)

Fix Steps

  1. 1 Check Ethernet cable link LED at adapter — must be solid green
  2. 2 Verify adapter power — module status LED should be green
  3. 3 Ping adapter IP from laptop on same network segment
  4. 4 Check for IP conflicts using RSLinx network browse
  5. 5 If on DLR ring, check ring status for open ring condition
  6. 6 Increase RPI if network is heavily loaded

Field Trick

The LINK led on the 1734-AENT adapter tells you everything. Green solid = cable good. Off = cable or switch issue. Flashing = traffic but no controller connection.