RepairXpert Industrial Automation

DeviceNet Scanner Communication Fault

AB-F021

DeviceNet scanner module lost communication with one or more nodes on the DeviceNet network.

high allen-bradley
allen-bradley devicenet communication scanner node

Probable Causes (ranked)

Fix Steps

  1. 1 Check scanner I/O tree — identify which node(s) lost communication
  2. 2 Verify node power and status LEDs
  3. 3 Check DeviceNet cable connections — reseat at problem node
  4. 4 Verify termination resistors on both ends of the trunk line
  5. 5 Check network power supply — must be 24VDC ±5%
  6. 6 Use DeviceNet network health analyzer if available

Field Trick

DeviceNet problems are almost always wiring. Check for the two 121-ohm termination resistors first — one missing resistor can take down the whole network.