Flex I/O module (1794 series) has faulted. Module may show red status LED. Typically found in remote I/O racks connected via DeviceNet, EtherNet/IP, or ControlNet.

high allen-bradley conveyor packaging palletizer piler
allen-bradley flex io 1794 io module remote io devicenet adapter

Probable Causes (ranked)

Fix Steps

  1. 1 Check module status LED — green=OK, red=fault, off=no power or dead
  2. 2 Reseat the module on its terminal base — push firmly until it locks in place
  3. 3 Check 24VDC power to the Flex I/O bank power supply — measure at terminals
  4. 4 Check adapter module (1794-AENT for EtherNet/IP or 1794-ADN for DeviceNet) status LEDs
  5. 5 If field wiring suspected, disconnect wiring from the faulted module — if fault clears, trace the field wiring
  6. 6 Verify module catalog number matches the PLC I/O configuration
  7. 7 If module is dead, swap with a spare — the terminal base retains all field wiring for fast swap