RepairXpert Industrial Automation

PowerFlex VFD Fault — Communication Loss (F081/F100 Series)

AB-PF-COMM

PowerFlex drive lost communication with the PLC over EtherNet/IP, DeviceNet, or embedded network port. Drive went to configured fault action (stop, coast, or hold last speed).

high allen-bradley conveyor packaging palletizer piler
allen-bradley powerflex vfd drive communication ethernet/ip network connection loss

Probable Causes (ranked)

Fix Steps

  1. 1 Check Ethernet cable at drive port and switch — verify link LED is lit on both
  2. 2 Ping the drive's IP address from a laptop to verify network connectivity
  3. 3 Power cycle the drive to reset the embedded communication adapter
  4. 4 In RSLogix 5000, check the drive's I/O connection status — look for specific CIP error codes
  5. 5 Verify drive IP address matches the PLC I/O configuration — use drive keypad menu or Rockwell BOOTP tool
  6. 6 Increase RPI (Requested Packet Interval) in the PLC I/O tree for this drive connection
  7. 7 Check PLC EN2T or embedded Ethernet port status — verify it is not overloaded with too many connections

Suggested Replacement Parts

Parts matched to fault category: Network Module

Allen-Bradley 1756-EN2T EtherNet/IP Module P/N: 1756-EN2T ControlLogix EtherNet/IP module, dual port, DLR capable
Siemens CM 1542-1 PROFINET Module P/N: 6GK7542-1AX00-0XE0 S7-1500 PROFINET IO controller, 2-port switch
Managed Industrial Ethernet Switch 8-Port P/N: SE2-SW5U 8-port managed switch, DIN rail, 10/100 Mbps, IGMP snooping

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes