PowerFlex drive DC bus voltage dropped below the minimum threshold. Drive cannot sustain motor operation. Typically caused by incoming power sag or loss.
PowerFlex drives log the DC bus voltage at the time of fault. Check parameter 'DC Bus Voltage' or the fault log — if the bus voltage is close to the trip point (typically 60% of nominal), the incoming power is marginal and you may need a line reactor or power conditioning.