Allen-Bradley PLC Minor Fault — EtherNet/IP Connection Loss (Type 20)

AB-PLC-MINOR20

A configured EtherNet/IP connection to a remote device has timed out. The connection faulted but the controller continues running. I/O data from the faulted connection is invalid.

high allen-bradley conveyor packaging palletizer piler asrs
allen-bradley plc controllogix compactlogix ethernet/ip connection minor fault network rpi

Probable Causes (ranked)

Fix Steps

  1. 1 In RSLogix 5000, expand I/O Configuration — find the module with yellow warning icon
  2. 2 Check Ethernet cable at both ends — verify link LED is lit on switch port and device port
  3. 3 Ping the remote device IP from a laptop on the same subnet — confirm network path is good
  4. 4 Power cycle the faulted remote device — wait 30 seconds for full restart
  5. 5 Check for duplicate IP addresses — use RSLinx Classic Browse or Rockwell BOOTP/DHCP tool
  6. 6 Increase RPI timeout in module connection properties if timeouts are intermittent under load
  7. 7 Check managed switch port status and VLAN configuration if applicable

Suggested Replacement Parts

Parts matched to fault category: Network Module

Allen-Bradley 1756-EN2T EtherNet/IP Module P/N: 1756-EN2T ControlLogix EtherNet/IP module, dual port, DLR capable
Siemens CM 1542-1 PROFINET Module P/N: 6GK7542-1AX00-0XE0 S7-1500 PROFINET IO controller, 2-port switch
Managed Industrial Ethernet Switch 8-Port P/N: SE2-SW5U 8-port managed switch, DIN rail, 10/100 Mbps, IGMP snooping

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes