Probable Causes (ranked)

Fix Steps

  1. 1 Access Stratix switch web interface — check port status page for error counts and port state
  2. 2 For DLR ring fault, check DLR status LED on switch — identify which ring port lost link
  3. 3 Check Ethernet cables on faulted port — replace if CRC error count is incrementing
  4. 4 If port is err-disabled, identify root cause (loop, broadcast storm) before re-enabling
  5. 5 Verify port speed matches connected device — set both to auto-negotiate or both to fixed 100Mbps full-duplex
  6. 6 For ring redundancy, walk the ring path physically — find the break point using link LEDs at each device

Field Trick

When a DLR ring breaks, all devices still communicate because the ring 'opens' into a linear chain. But you now have zero redundancy. The Stratix ring supervisor LED goes from GREEN to RED. Fix the break ASAP — the next cable failure takes the whole network down.