RepairXpert Industrial Automation

VFD Motor Overload

VFD-MOL1

VFD electronic motor overload protection tripped. Motor current exceeded the programmed overload threshold for the programmed time.

medium vfd conveyor packaging palletizer
vfd motor overload thermal fan cooling

Probable Causes (ranked)

Fix Steps

  1. 1 Check motor nameplate FLA and verify VFD motor overload parameter matches
  2. 2 Measure actual motor current with clamp meter — compare to FLA
  3. 3 Check motor surface temperature with IR gun — should not exceed nameplate insulation class rating
  4. 4 Inspect motor fan and fan shroud — clear debris, verify fan spins freely
  5. 5 If running continuously below 30Hz on a TEFC motor, add a forced-cooling blower kit
  6. 6 Check mechanical load — rotate shaft by hand with motor disconnected, feel for binding

Field Trick

If a motor runs fine for 2 hours then trips on overload, check the motor fan shroud first. A clogged shroud lets the motor slowly heat up until the thermal model trips. Cleaning the shroud takes 5 minutes and is the fix 40% of the time.