VFD DC Bus Overvoltage

VFD-OV1

DC bus voltage exceeded safe threshold. Typically caused by regenerative energy from the motor during deceleration.

high vfd conveyor palletizer
vfd overvoltage dc bus braking regeneration

Probable Causes (ranked)

Fix Steps

  1. 1 Increase deceleration time — double it and test
  2. 2 Verify braking resistor: measure resistance, check wiring to drive BR terminals
  3. 3 Measure incoming voltage at drive input — should be within ±10% of drive rating
  4. 4 Enable coast-to-stop if application allows — eliminates regen entirely
  5. 5 Check drive DC bus voltage on parameter display — should be ~1.35x line voltage at rest
  6. 6 For high-inertia loads, size braking resistor for continuous duty
  7. 7 Verify braking transistor with drive diagnostic test

Field Trick

Set decel time to 999 seconds temporarily. If OV goes away, it's a regen problem. Size a braking resistor.