RepairXpert Industrial Automation

VFD Safe Torque Off Active

VFD-STO1

Drive Safe Torque Off (STO) function is active. Drive output is disabled by safety circuit — motor cannot run.

medium vfd allen-bradley
vfd sto safe torque off safety drive enable

Probable Causes (ranked)

Fix Steps

  1. 1 Check STO terminal — should have 24VDC when safe to run
  2. 2 Trace STO wiring back to safety relay or PLC safety output
  3. 3 If STO not used, jumper the STO terminals per drive manual
  4. 4 Reset safety relay if tripped — investigate why it tripped
  5. 5 Check E-stop circuit — all stations released and circuit complete

Field Trick

Put your meter on the STO terminals. 24V = safe to run, should start. 0V = safety circuit open, trace it back.

Suggested Replacement Parts

Parts matched to fault category: Safety Relay

Allen-Bradley Guardmaster 440R-N23126 P/N: 440R-N23126 Dual-channel safety relay, 24VDC, 3 N.O. + 1 N.C., Cat 4 / PLe
Pilz PNOZ X3 Safety Relay P/N: 774310 24VDC/AC, 3 N.O. + 1 N.C., E-stop and safety gate monitoring

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes